SOUTH CABLE
XHHW-2 Aluminum Conductor
Voltage:600V
Structure:ConductorClass B stranded bare aluminum per ASTM B800 and ASTM B801
InsulationHeat and moisture resistant cross-linked polyethylene (XLPE) insulation in various colors
Insulation ColourBlack, Customized as needed


Overview Specifications FAQ Test&Acceptance Send Message

APPLICATION

XHHW-2 Wire can be used as a building line, widely used in highrise buildings, subways, commercial offices and other large public places, can also be used in photovoltaic power stations, mobile energy storage power stations, wind energy storage systems and other new energy fields.

XHHW

UL44 certified XHHW‑2 aluminum building wire, Heat‑moisture resistant XLPE insulation, 90℃ wet‑dry rating, widely used for indoor‑outdoor commercial, industrial power distribution wiring.

CHARACTERISTICS

Voltage Rating Uo/U

600V

Temperature Rating

-40°C to 90°C

STANDARDS

ASTM B800 8000 Series Aluminum Alloy Wire

ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy

UL 44 - Thermoset-Insulated Wires and Cables

UL 1581 - Flame Exposure Test

National Electrical Code (NEC)

CONSTRUCTION

Conductor

Class B stranded bare aluminum per ASTM B800 and ASTM B801

Insulation

Heat and moisture resistant cross-linked polyethylene (XLPE) insulation in various colors

Sheath Colour

Black, Customized as needed

SIZE (AWG OR KCMIL)STRAND
QTY.
Nominal Insulation ThicknessOUTSIDE DIAMETERAPPROX. NET WEIGHTALLOWABLE AMPACITY1 (AMPS)
MMINMMINKG/MILLBS/1000FT75º C90º C
871.140.0455.990.23642284045
671.140.0456.960.27460405055
471.140.0458.180.32286586575
271.140.0459.700.3821288690100
1191.400.05510.600.417164110100115
1/0191.400.05511.500.453200134120135
2/0191.400.05512.600.496243163135150
3/0191.400.05513.800.543299201155175
4/0191.400.05515.100.594368247180205
250371.650.06516.700.657442297205230
300371.650.06518.000.709523351230260
350371.650.06519.200.756599402250280
400371.650.06520.200.795676454270305
500371.650.06522.200.874830557310350
600612.030.0824.900.981014681340385
750612.030.0827.301.0751244835385435
1000612.030.0831.201.22816271092445500


  • Who we are?

    SOUTH CABLE is a company specializing in the research, development, manufacturing,and sales of high-end wire and cable products.

  • How can we guarantee quality?

    Always a pre-production sample before mass production; Always final Inspection before shipment.

  • What can you buy from us?

    Wire, Cable


  • Why should you buy from us not from other suppliers?

    We have CSA and CUL certifications, We have Fifteen years of experience in design and development.

  • What services can we provide?

    Accepted Delivery Terms: FOB,CFR,CIF,EXW;
    Accepted Payment Currency:USD,EUR;
    Accepted Payment Type:T/T,L/C,Money Gram,Western Union;Language Spoken:English,Chinese,French


  • How long does it take to get a quote back

    Most quotes are returned within 24 hours

TEST

Tests are divided into routine tests, sampling tests and type test items.

1.Routine tests

routine tests: Tests carried out by the manufacturer on all manufactured lengths of finished cables toverify that all cables comply with specified requirements.Routine test items :Conductor resistance measurement, voltage test.

2.Sampling tests

Sampling tests: Tests carried out by the manufacturer on specimens of finished cables or on certaincomponents taken from finished cables at specified frequencies to check whether the cables complywith specified requirements.

Sampling test items:Conductor inspection, dimensional inspection,thermal extension testing ofinsulation and elastomer sheaths.

3.Type test

Type test:Tests carried out on normal commercial principles before supply of a type of cable covered by this standard to demonstrate that the cable has satisfactory performance under the conditions of intended use.

Type testing includes electrical type testing and non-electrical type testing items.

Electrical type test items:1) Insulation resistance measurement at ambient temperature.2) Measurement of insulation resistance at maximum conductor temperature during normal operation.3) 4h voltage test.

Non-electrical type test items include insulation non-electrical type test and sheath non-electrical type test.

Insulation non-electrical type test items: Dimensional measurements、mechanical properties(tensile strength and Elongation at break)、High temperature pressure test、Low temperature performance、Thermal shock test、Thermal extension test and water absorption test, etc.

Sheath non-electrical type test items:Dimensional measurements、mechanical properties(tensile strength and Elongation at break)、High temperature pressure test、Low temperature performance、Weight loss test and thermal shock test, etc.


Name:
E-mail:*
Phone:*
Country:
Message:*